Home
About Us
On-Line Ordering
Sprinklers
Timers
Valves
Rotator Nozzles
Drip Irrigation
Do it Yourself Kits
Do it Yourself Seminar
Accessories
Service
Request a Quote
Landscape Lighting
Download Manuals
Specials
Winterizing Info
Ever Wonder What Makes Up The Price Of An Irrigation System?
New Products
Toro
Irritrol
Rainbird
Hunter
Orbit
Contact Us
FAQ
Employment
Find a Contractor in your Area
Advertise Your Company

 

lawnsprinklers, lawn sprinklers, winterizing, winter, fall blow out, blow outs, winterizing, startup, tor
Installation - Service - Do-it-yourself Kits
Spring Openings - Fall Closings
Residential & Commercial
Parts - Design Services

Winterizing Your Sprinklers

Tips From Rain Bird to Help Keep Your Sprinklers Safe Until Next Spring
CAUTION! WEAR PROPER EYE PROTECTION!
Extreme care must be taken when blowing out the system to avoid excessive pressure which can damage valves or sprinkler pipe or cause physical injury due to flying debris. Do not stand over any irrigation components (pipes, sprinklers, and valves) during air blow out. Air pressure must not exceed 50 pounds per square inch (psi).
 

Without proper preparation your sprinkler system can be damaged by freezing temperatures. Here are some tips from Rain Bird on how to prepare your irrigation system if you live in a region where it freezes.

1. Insulate your assets.

Shut off the water supply to the irrigation system. The main shut off valve for your irrigation system needs to be protected against freezing. To prevent it from freezing make sure it is wrapped with insulation (foam insulation tape and a plastic bag), or somehow protected from freezing. If you do not have a main shut off valve, consider it a preventative investment. Any above ground piping needs to be insulated. Self-sticking foam-insulating tape or foam insulating tubes commonly found at home supply stores, are fine.

2. Stay in control.

If you have an automatic system then you will need to "shut down" the controller (timer). Most controllers have a “rain-mode" which simply shuts off the signals to the valves. The controller continues to keep time, the programming information (start times, valve run times, etc,) isn't lost, and the clock continues to run. The only change is that the valves will not activate. If your controller is responsible for activating a pump, as a precaution, remove the wires that are connected to the MV and common. This will prevent the possibility of the pump from being activated which could cause overheat damage.

An alternative to using the rain mode is simply to shut off the power to the controller. If you do, you'll need to reprogram the time and potentially all your other settings as well, in the spring.

3. Drain the pipes.

Now you need to remove the water from the pipes and sprinklers so that it won't freeze and break the pipe. There are several ways to drain your pipes: the manual drain valve, the automatic drain valve or the compressed air blow-out methods. However, since there could be potential safety risks we recommend contacting your local irrigation specialist.

4. Protect valves and backflow preventers.

Insulate backflow preventers and valves if they are above ground. You can also use insulation tape for this. Do not block the air vents and drain outlets on backflow preventers.

Please review the Rain Bird Homeowner's Guide to Winterization for detailed instructions on how to prepare your irrigation system for the Winter months.

Rain Bird Homeowner's Guide to Winterization
http://www.rainbird.com/pdf/diy/WinterizationGuide.pdf


Winterizing Your Irrigation System
Courtesy of Hunter

Every year, before the first freeze, the ritual of irrigation "blow out" becomes the priority for all irrigation systems that are in parts the country where the frost level extends below the depth of the installed piping.

Even if you have drained some water out of the system, the remaining water can freeze, expand and crack the PVC piping (rigid, white pipe), usually from fitting to fitting. Polyethylene pipe (flexible, black pipe) is used in many freezing climates. Although polyethylene pipe is more flexible and can expand under pressure, water left inside could freeze and rupture the pipe walls. Freezing water in the backflow assembly will damage the internal components and could possibly crack the brass body.

To minimize the risk of freeze damage to your irrigation system, you’ll need to "winterize" your irrigation system

Irrigation systems in areas where "winterization" is mandatory are installed using one of three types of water removal in mind: manual drain, auto drain, or blowout. If you don’t know your system type, it would be best to use the blowout method.

Manual Drain Method
Use when manual valves are located at the end and low points of the irrigation piping. To drain these systems, simply shut off the irrigation water supply (shut off will be located in the basement and will be either a gate/globe valve, ball valve or stop and waste valve - see drawings below) and open all the manual drain valves. Once the water has drained out of the mainline, open the boiler drain valve or the drain cap on the stop and waste valve (whichever is used in your area) and drain all the remaining water that is between the irrigation water shut off valve and the backflow device. Open the test cocks on the backflow device. If your sprinklers have check valves you’ll need to pull up on the sprinklers to allow the water to drain out the bottom of the sprinkler body. Depending on the location of the drain valves, there could be some water left in the backflow, the piping and the sprinklers. When all the water has drained out, close all the manual drain valves.

Automatic Drain Method
Use when automatic drain valves are located at the end and low points of the irrigation piping. These will automatically open and drain water if the pressure in the piping is less than 10 PSI. To activate these, you shut off the irrigation water supply (shut off will be located in the basement and will be either a gate/globe valve, ball valve or stop and waste valve - see drawings below) and activate a station to relieve the system pressure. Once the water has drained out of the mainline, open the boiler drain valve or the drain cap on the stop and waste valve (whichever is used in your area) and drain the remaining water that is between the irrigation water shut off valve and the backflow device. Open the test cocks on the backflow device. If your sprinklers have check valves you’ll need to pull up on the sprinklers to allow the water to drain out the bottom of the sprinkler body. Depending on the location of the drain valves, there could be some water left in the backflow, the piping and in the sprinklers.

In some areas you might have a combination of the manual drain system on the mainline (the pipe between the irrigation water shut off valve and the valves) and auto drain system on the lateral lines (the pipe between the valves and the sprinklers).

"Blow Out" Method
It is recommended that a qualified licensed contractor perform this type of "Winterization" method, The blow out method utilizes an air compressor with a Cubic Foot per Minute (CFM) rating of 80-100 for any mainline of 2" or less. These types of compressors can be rented at your local equipment rental yard. The compressor is attached to the mainline via a quick coupler, hose bib or other type connection, which is located after the backflow device. Compressed air should not be blown through any backflow device. To start the "blow out", shut off the irrigation water supply and, with the compressor valve

in the closed position, attach the air compressor hose to the fitting. Activate the station on the controller that is the zone or sprinklers highest in elevation and the furthest from the compressor. Close the backflow isolation valves. Then slowly open the valve on the compressor; this should gradually introduce air into the irrigation system. The air pressure should be constant at 50 PSI. If the sprinkler heads do not pop up and seal, increase the air pressure until the heads do pop up and seal. The air pressure should NEVER exceed 80 PSI.

Each station/zone should be activated starting from the furthest station/zone from the compressor slowly working your way to the closest station/zone to the compressor. Each station/zone should be activated until no water can be seen exiting the heads, this should take approximately two minutes or more per station/zone. It is better to use two or three short cycles per station/zone than to have one long cycle. Once the station/zone is dry, you should not continue to blow air through the pipe. Compressed air moving through dry pipes can cause friction, which will create heat and the heat could cause damage.

Additional Steps
Once the water has been removed from the irrigation system, disconnect the air compressor and release any air pressure that may be present. If your backflow device, the most common backflow installed is called a Pressure Vacuum Breaker, has ball valves, open and close the isolation valves on the backflow device numerous times to ensure that any trapped water has escaped from the upper areas. Leave the isolation valves open at a 45° angle (approximately 1/2 open) and open the test cocks.

Pressure Vacuum Breaker

Pressure Vacuum Breaker

Pressure Vacuum Breaker

  1. PVB Test Cocks
  2. Isolation Ball Valve Inlet
  3. Isolation Ball Valve Outlet
 

Interior Point of Connection Freezing Climates

Interior Point of Connection Freezing Climates

  1. Boiler Valve
  2. Irrigation Shut Off Valve
  3. Main Water Shut Off Valve
  4. Water Meter

Types of Valves

Gate Valve
Ball Valve
Stop and Waste Valve
Boiler Valve
Gate Valve
Ball Valve
Stop & Waste Valve
Boiler Valve

 

Preparing a hydraulic control system? Shut off the water supply to the signal control tube(s) and drain the field tubing.

Outdoor mounted controllers? Leave the power on and the dial / switch in the "Off" position. The heat from the transformer will keep the enclosure warm enough to keep condensation from forming inside the controller enclosure. The dial in the "OFF" will keep the controller from activating the solenoids in the field.

Indoor mounted controllers? You may either leave the power on and the dial/switch in the "Off" position OR you may remove the battery backup and unplug the transformer.

Rain Sensors? There is not much to do to prepare the rain sensor for the winter months. If your sensor is the type with a cup or bowl that catches water, you might want to remove the water and place a plastic bag over the sensor. This will keep any water from accumulating and freezing in the cup or bowl area. If your sensor is the type that uses wafers or discs, you might want to remove the wafers and store them in the garage for the winter months. This will keep damp wafers from freezing.

The Do NOTS of "BLOW~OUT" Winterization
Do not allow the air pressure to exceed 80 PSI for systems with PVC piping and 50 PSI for systems with polyethylene piping.
Do not stand over component parts while the system is pressurized with air.
Do not leave the air compressor unattended.
Do not blow the system out through a backflow or pump. First blow out the system, then drain the backflow or pump.
Do not leave the manual drain valves open after the blow out.

Download a PDF from Hunter
Fill in a Quote or Repair request form


 
Visit Our Landscape Lighting Section
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Water Works Irrigations & Illuminations Ltd.
2839 Hwy. 2 East - Just East of the Zoo
Bowmanville, Ontario  905 623-9165
Serving: The Durham Region, Peterborough, Cobourg & Port Hope
Member of Landscape Ontario  -  Member of CNLA   -  Team TORO Professional Contractor
Certified TORO Intelli-Sense™ Technician
Dealer for: Toro - Rain Bird - Hunter - Irritrol - Orbit - Nelson