CAUTION!
WEAR PROPER EYE PROTECTION!
Extreme care must be taken when blowing out the
system to avoid excessive pressure which can damage
valves or sprinkler pipe or cause physical injury
due to flying debris. Do not stand over any irrigation
components (pipes, sprinklers, and valves) during
air blow out. Air pressure must not exceed 50
pounds per square inch (psi).
Without
proper preparation your sprinkler system can be
damaged by freezing temperatures. Here are some
tips from Rain Bird on how to prepare your irrigation
system if you live in a region where it freezes.
1.
Insulate your assets.
Shut
off the water supply to the irrigation system.
The main shut off valve for your irrigation system
needs to be protected against freezing. To prevent
it from freezing make sure it is wrapped with
insulation (foam insulation tape and a plastic
bag), or somehow protected from freezing. If you
do not have a main shut off valve, consider it
a preventative investment. Any above ground piping
needs to be insulated. Self-sticking foam-insulating
tape or foam insulating tubes commonly found at
home supply stores, are fine.
2.
Stay in control.
If
you have an automatic system then you will need
to "shut down" the controller (timer).
Most controllers have a “rain-mode"
which simply shuts off the signals to the valves.
The controller continues to keep time, the programming
information (start times, valve run times, etc,)
isn't lost, and the clock continues to run. The
only change is that the valves will not activate.
If your controller is responsible for activating
a pump, as a precaution, remove the wires that
are connected to the MV and common. This will
prevent the possibility of the pump from being
activated which could cause overheat damage.
An
alternative to using the rain mode is simply to
shut off the power to the controller. If you do,
you'll need to reprogram the time and potentially
all your other settings as well, in the spring.
3.
Drain the pipes.
Now
you need to remove the water from the pipes and
sprinklers so that it won't freeze and break the
pipe. There are several ways to drain your pipes:
the manual drain valve, the automatic drain valve
or the compressed air blow-out methods. However,
since there could be potential safety risks we
recommend contacting your local irrigation specialist.
4.
Protect valves and backflow preventers.
Insulate
backflow preventers and valves if they are above
ground. You can also use insulation tape for this.
Do not block the air vents and drain outlets on
backflow preventers.
"Blow
Out" Method
It is recommended that a qualified licensed contractor
perform this type of "Winterization"
method, The blow out method utilizes an air compressor
with a Cubic Foot per Minute (CFM) rating of 80-100
for any mainline of 2" or less. These types
of compressors can be rented at your local equipment
rental yard. The compressor is attached to the
mainline via a quick coupler, hose bib or other
type connection, which is located after the backflow
device. Compressed air should not be blown through
any backflow device. To start the "blow out",
shut off the irrigation water supply and, with
the compressor valve
in
the closed position, attach the air compressor
hose to the fitting. Activate the station on the
controller that is the zone or sprinklers highest
in elevation and the furthest from the compressor.
Close the backflow isolation valves. Then slowly
open the valve on the compressor; this should
gradually introduce air into the irrigation system.
The air pressure should be constant at 50 PSI.
If the sprinkler heads do not pop up and seal,
increase the air pressure until the heads do pop
up and seal. The air pressure should NEVER exceed
80 PSI.
Each
station/zone should be activated starting from
the furthest station/zone from the compressor
slowly working your way to the closest station/zone
to the compressor. Each station/zone should be
activated until no water can be seen exiting the
heads, this should take approximately two minutes
or more per station/zone. It is better to use
two or three short cycles per station/zone than
to have one long cycle. Once the station/zone
is dry, you should not continue to blow air through
the pipe. Compressed air moving through dry pipes
can cause friction, which will create heat and
the heat could cause damage.
Additional
Steps
Once the water has been removed from the irrigation
system, disconnect the air compressor and release
any air pressure that may be present. If your
backflow device, the most common backflow installed
is called a Pressure Vacuum Breaker, has ball
valves, open and close the isolation valves on
the backflow device numerous times to ensure that
any trapped water has escaped from the upper areas.
Leave the isolation valves open at a 45° angle
(approximately 1/2 open) and open the test cocks.
|